Moisture measurement in SF6-insulated switchgear is vital. That?s why WIKA has improved the performance of the GDHT-20 sensor for this industry. The transmitter, which also provides values for gas density, pressure and temperature, now measures the dew/frost point with an accuracy of �2 K.
Moisture, along with density, may be the crucial parameter for assessing the condition of the SF6 gas used. The GDHT-20 continuously monitors its content in the gas. The info from the online monitoring forms the input for a downstream trend analysis. The more precise both density and the moisture measurement are, the more precise this analysis will be.
Predictive maintenance instead of regular maintenance intervals
The model GDHT-20 sensor can be an all-in-one instrument for the online monitoring of SF6-insulated switchgear. It works with three temperature sensors (red), a pressure sensor (blue) and a humidity sensor (yellow).
The analysis shows the operator when the SF6 will reach a crucial state so when remedial measures should be taken. Subsequently, maintenance work or gas treatment is only undertaken when action is actually needed. Predictive maintenance thus replaces the sequence of regular maintenance intervals that has been previously necessary to avoid ecological and safety risks.
An excessive amount of moisture in the gas compartment is one of these brilliant risks. In pressure gauge , moisture mainly increases due to permeation through sealing materials. In pressure gauge 10 bar , this is usually due to moisture remaining on metal surfaces or in insulation materials during tank assembly, because of incomplete evacuation before initial filling with SF6.
Excessive moisture content leads to corrosive reaction products that may damage internal components and shorten the service life. If such substances escape, there is yet another danger to people?s health.
SF6 moisture measurement parameters
Measurement of SF6 moisture is therefore indispensable. In most cases, the dew or frost point is used as a parameter. This is the temperature at which the air humidity begins to condense. In the case of SF6, the atmospheric dew point specified by IEC 60376 is -36 �C.
The accuracy of the GDHT-20 of �2 K for moisture measurement is validated at the frost point with an internationally valid reference standard. However, the measuring instrument can be configured for other parameters (dew point, ppmv, ppmw and relative humidity). The new version of the sensor also features greater application flexibility. The GDHT-20 is now also suitable for density monitoring of the alternative insulating gases N2, CF4, O2, CO2 and 3MTM NovecTM 4710.
Note
More info on the GDHT-20 sensor are available on the WIKA website. If you have any questions, your contact will gladly assist you to.